Technical data
AirAdapt 3-12 AirAdapt 4-16 AirAdapt 4-20Heating A7/W35
Work modulation mode
inverter
inverter
inverter
Minimum and maximum heating power in A7W35
3,00 – 13,65 kW
4,70 – 17,85 kW
4,70 – 21,40 kW
Set compressor speed
26%
30%
26%
Rated thermal power
6,460 kW
9,192 kW
9,406 kW
Electrical power consumption
1,222 kW
1,734 kW
1,707 kW
COP efficiency level
5,286
5,301
5,511
Heating A7/W55
Set compressor speed
32%
36%
32%
Rated thermal power
6,038 kW
9,062 kW
9,539 kW
Electric power consumption
1,894 kW
2,705 kW
2,668 kW
COP efficiency level
3,187
3,350
3,576
Heating A-10/W55
Set compressor speed
100%
100%
100%
Rated thermal power
8,146 kW
10,020 kW
12,303 kW
Electric power consumption
3,762
4,670
5,658
COP efficiency level
2,165
2,146
2,174
Basic parameters
Refrigerant/charge
R290/1,65 kg
R290/2,0 kg
R290/2,40 kg
Maximum supply temperature
75°C
75°C
75°C
Sound power level
56 db(A)
58 db(A)
59,5 db(A)
Scales
200 kg
210 kg
215 kg
Energy class – moderate climate, low-temperature installation
A+++
A+++
A+++
Energy class – moderate climate, medium temperature installation
A+++
A+++
A+++
Evaporator reverse defrost
YES
YES
YES
Power supply
3x 400 V
3x 400 V
3x 400 V
External dimensions
Height (A)
1166 mm
1166 mm
1366 mm
Depth (B)
595 mm
595 mm
595 mm
Length (C)
1300 mm
1400 mm
1400 mm
Leg spacing, length (D)
1180 mm
1280 mm
1280 mm
Leg spacing, depth (E)
470 mm
475 mm
475 mm
Other dimensions
heating circuit connection diameter
1”
5/4”
5/4”
Location of the heating circuit connection – dimension F
32 mm
47 mm
47 mm
Location of the heating circuit connection – dimension G
177 mm
124 mm
124 mm
Location of the heating circuit connection – dimension H
247 mm
224 mm
224 mm
Location of condensate drain – dimension I
554 mm
570 mm
570 mm
Condensate drain location – dimension J
93 mm
94 mm
94 mm
Other parameters
Heating water temperature adjustment range
+20°C up to +65°C
+20°C up to +65°C
+20°C up to+65°C
Outside air temperature range for heat pump operation
-25°C up to +35°C
-25°C up to +35°C
-25°C up to +35°C
Number of compressors
1 piece
1 piece
1 piece
Maximum operating pressure of the heat pump’s central heating refrigeration circuit
32 bar
32 bar
32 bar
Air volume flow at maximum compression
5800 m3/h
6300 m3/h
7000 m3/h
Required water volume flow
1700 l/h
2100 l/h
2500 l/h
Maximum operating pressure of the central heating circuit
2,5 bar
2,5 bar
2,5 bar
Hermetic cooling system
Yes
Yes
Yes